The brief this answer responds to
For information and reference only – not to be submitted as your own work. This is a learning extract that shows the method behind a shell-and-tube design calculation. Every figure is illustrative and rests on stated approximate assumptions. If your course prohibits generative AI or outside help for the assessment, follow those rules: use this […]
For information and reference only – not to be submitted as your own work. This is a learning extract that shows the method behind a shell-and-tube design calculation. Every figure is illustrative and rests on stated approximate assumptions. If your course prohibits generative AI or outside help for the assessment, follow those rules: use this page to understand the method, then do your own work.
Modules coded B50TE (Heat Exchangers and Heat Transfer) typically ask for a justified TEMA AEU U-tube design (Tubular Exchanger Manufacturers Association, 2019) that recovers heat in a whisky-distillery setting: a hot, nearly alcohol-free by-product (pot ale) pre-heats the cold feed (wash, a roughly 9% ABV water–ethanol mixture). This extract covers the calculation spine that markers look for in the manual-check tasks: heat duty, temperature profile, LMTD with an F correction, tube-side coefficient from forced-convection correlations, and the area check. It does not reproduce any HTRI Xchanger output; the shell-side coefficient is an assumed placeholder, and your own report must use your own software results. The full brief is on our B50TE heat exchangers Assignment #1 question page.
1. Basis and assumptions (illustrative)
All values below are approximate working assumptions for demonstration, not measured data. Fluids stay liquid, the hot stream (pot ale, treated as water) is on the tube side, the wash is on the shell side, and the exchanger is modelled as identical 1-2 shells in series.
| Item | Wash (cold, shell side) | Pot ale (hot, tube side) |
|---|---|---|
| Inlet temperature | 35 °C | 85 °C |
| Volumetric flow (chosen) | 550 L/min | 550 L/min |
| Density (approx.) | 975 kg/m³ (about 7% ethanol by mass) | 970 kg/m³ at inlet; 978 kg/m³ at mean tube temperature |
| Specific heat (approx.) | 4.10 kJ/kg·K (water–ethanol mix, mixing-rule estimate) | 4.19 kJ/kg·K (water) |
| Viscosity / conductivity (approx.) | not needed for the duty | 0.40 mPa·s, 0.66 W/m·K |
| Target outlet | 70 °C (above the 66 °C requirement) | result of the heat balance |
Tube geometry assumed: 19.05 mm outside diameter, 15.75 mm inside diameter, carbon-steel wall (k = 16 W/m·K), 60 tubes per pass, fouling resistance 0.0002 m²·K/W on each side, and a shell-side coefficient of 3,000 W/m²·K taken as a stand-in for the figure your software would report. The 9% ABV wash is about 7% ethanol by mass, so mixture properties are weighted estimates; in a real submission, take them from the property package and state the source.
2. Heat balance (duty)
Wash mass flow = 550/60/1000 × 975 = 8.94 kg/s. Duty Q = ṁcΔT = 8.94 × 4.10 × (70 − 35) = 1,282.5 kW. Pot ale mass flow is 8.89 kg/s, so its outlet temperature is 85 − 1,282.5/(8.89 × 4.19) = 50.6 °C.
The pot ale outlet (about 51 °C) is cooler than the wash outlet (70 °C). That is a temperature cross, which strongly limits what a single shell pass can do and drives the design decision in Section 3.
3. LMTD, correction factor and number of shells
Counter-current terminal differences are ΔT₁ = 85 − 70 = 15.0 K and ΔT₂ = 50.6 − 35 = 15.6 K, giving LMTDcf = 15.29 K. The dimensionless groups are R = (85 − 50.6)/(70 − 35) = 0.984 and P = (70 − 35)/(85 − 35) = 0.70.
For one 1-2 shell the maximum attainable P at this R is 0.591, so P = 0.70 is impossible in one AEU shell. Splitting the duty over N identical shells in series reduces the P each shell must achieve; the standard F expression (Bowman et al., 1940; Kakaç et al., 2020) then gives:
| Shells in series | P per shell | F | Comment |
|---|---|---|---|
| 1 | 0.700 | none (above P limit) | Infeasible |
| 2 | 0.536 | 0.726 | Feasible, but F is low and tubes become very long |
| 3 | 0.434 | 0.896 | Chosen for this extract |
The corrected mean difference is F × LMTDcf = 0.896 × 15.29 = 13.69 K. A sensible report would also test what happens with a different pot ale flow. With the lower flow of 400 L/min, the pot ale outlet would be about 37.7 °C and a single shell could not exceed a wash outlet of about 59.8 °C, below the 66 °C requirement. That comparison shows markers why the flow rate and shell count were chosen, not just stated.
Need to see how a full heat-exchanger design report is structured? Our engineering team can explain the method and layout.
4. Tube-side heat transfer coefficient
Tube velocity v = Qv/(Nt × Aflow) = 0.009167/(60 × 1.948×10⁻⁴) = 0.78 m/s. Reynolds number Re = ρvd/μ = 30,197, so the flow is fully turbulent. Prandtl number Pr = cpμ/k = 2.54.
Dittus–Boelter form (cooling fluid, n = 0.3; Bergman et al., 2011): Nu = 0.023 Re0.8 Pr0.3 = 116.7, so hi = Nu k/d = 4,891 W/m²·K.
Gnielinski (Gnielinski, 2010): f = (0.79 ln Re − 1.64)⁻² = 0.0236; Nu = (f/8)(Re − 1000)Pr / [1 + 12.7 √(f/8) (Pr2/3 − 1)] = 137.2, giving hi = 5,750 W/m²·K. Gnielinski is about 18% higher here, which is typical because it is valid for a wider Re range and is fitted to a friction factor. Compare whichever value you use with the software figure and explain any gap (property package, wall-temperature correction, tube-side model).
Mixture note: the hot stream here is treated as water because pot ale carries little ethanol. If the wash (the water–ethanol mixture) were on the tube side, use mixture density, viscosity, conductivity and specific heat at the mean bulk temperature, not a linear average of the pure-component values, because viscosity of water–ethanol is strongly non-linear.
5. Overall coefficient and area check
Referred to the outside area: 1/Uo = 1/ho + Rf,o + do ln(do/di)/(2kw) + Rf,i do/di + do/(dihi). With the Gnielinski value, Uo = 910 W/m²·K; with Dittus–Boelter, 880 W/m²·K.
| Quantity | Dittus–Boelter basis | Gnielinski basis |
|---|---|---|
| Tube-side h (W/m²·K) | 4,891 | 5,750 |
| Overall Uo (W/m²·K) | 880 | 910 |
| Required area A = Q/(U F LMTD) (m²) | 106.4 | 102.9 |
| Area per shell, 3 shells (m²) | 35.5 | 34.3 |
| Tube length per shell (m) | 4.94 | 4.78 |
The two correlations differ by only about 3.4% in required area because the fouling and shell-side resistances dominate. Without the F correction the same duty would appear to need only 92.2 m², about 10% too small, which is the error a marker expects you to avoid. When you compare with a software area, discuss differences in shell-side coefficient, baffle arrangement, tube-count limits and the software’s own fouling treatment.
6. Trade-offs and parameter effects
Tube count per pass sets velocity (heat transfer and fouling) against pressure drop; the wash target sets duty and the temperature cross. The table varies each individually and together at the same assumptions (3 shells, Gnielinski basis).
| Case | Q (kW) | Pot ale out (°C) | v (m/s) | hi | F | Area (m²) | L per shell (m) | Tube-side friction Δp, all shells (kPa) |
|---|---|---|---|---|---|---|---|---|
| Base: 60 tubes/pass, wash 70 °C | 1,283 | 50.6 | 0.78 | 5,750 | 0.896 | 102.9 | 4.78 | 12.9 |
| A: 45 tubes/pass | 1,283 | 50.6 | 1.05 | 7,311 | 0.896 | 98.7 | 6.11 | 27.4 |
| B: wash outlet 66 °C | 1,136 | 54.5 | 0.78 | 5,750 | 0.951 | 68.2 | 3.16 | 8.6 |
| A + B together | 1,136 | 54.5 | 1.05 | 7,311 | 0.951 | 65.4 | 4.05 | 18.2 |
Change A raises velocity and hi by 27%, but the area only falls by 4% because other resistances remain; tubes lengthen by 28% and friction loss roughly doubles. Change B cuts duty by 11% and relaxes the cross, so F rises to 0.95 and area drops by about 34%, at the price of a cooler wash. Together the effects are not additive, since the lower duty also shortens the tubes needed. All friction losses sit well inside the 50 kPa allowance before nozzle and return losses, which you should still add.
Practical comment for a report: 0.78 m/s is modest for a stream with suspended solids, so a velocity-versus-fouling argument (or a supplementary-heating option if the 66 °C minimum cannot be guaranteed) should appear in the justification.
Companion guide: how to structure a shell-and-tube design report and what markers reward. Related: engineering report writing support.
About the expert
Reviewed by Nada Ahmed. Her profile lists Thermodynamics & Heat Transfer as her field and a Bachelor’s in Mechanical Engineering from Jumeirah College.
Want a similar reference extract explained step by step for your own data? Share your brief and we will talk you through the method.
References
- Bergman, T. L., Lavine, A. S., Incropera, F. P., & DeWitt, D. P. (2011). Fundamentals of heat and mass transfer (7th ed.). Wiley.
- Bowman, R. A., Mueller, A. C., & Nagle, W. M. (1940). Mean temperature difference in design. Transactions of the ASME, 62, 283–293.
- Gnielinski, V. (2010). G1 Heat transfer in pipe flow. In VDI heat atlas (2nd ed., pp. 691–700). Springer.
- Kakaç, S., Liu, H., & Pramuanjaroenkij, A. (2020). Heat exchangers: Selection, rating, and thermal design (4th ed.). CRC Press.
- Tubular Exchanger Manufacturers Association. (2019). TEMA standards (10th ed.). TEMA.
This page is public, so Turnitin has already seen it
Read it for structure, sourcing and depth. Submitting any part of it is caught immediately. Your own brief will differ from this one, and so should your answer.